PK5522
Pressure switch with intuitive switch point setting
PK-100-SFG14-PSPKG/US/ /W
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — PK5522-00 — 29.04.2014 —
Outputs
Total number of outputs
1
Output signal
switching signal
Electrical design
PNP
Number of digital outputs
1
Output function
normally open
Max. voltage drop switching
output DC
[V]
2
Permanent current rating of
switching output DC
[mA]
500
Switching frequency DC [Hz]
100
Short-circuit protection
yes
Type of short-circuit
protection
pulsed
Overload protection
yes
Measuring/setting range
Measuring range 0...100 bar 0...1450 psi
Set point SP 3...100 bar 44...1450 psi
Hysteresis 2 bar 29 psi
Accuracy / deviations
Switch point accuracy
[% of the final value]
< ± 2,5; (Setting accuracy)
Repeatability
[% of the final value]
< ± 0,5; (with temperature fluctuations < 10 K)
Characteristics deviation
[% of the final value]
< ± 1,5 (BFSL) / < ± 2,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Temperature drift per 10 K
< ± 0.5
Software / programming
Adjustment of the switch
point
setting ring
Operating conditions
Ambient temperature [°C]
-25...80
Storage temperature [°C]
-40...100
Protection
IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance DIN IEC 68-2-27 50 g (11 ms)
Vibration resistance DIN IEC 68-2-6 20 g (10...2000 Hz)
MTTF [years]
1030
Pressure Equipment Directive
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request